What are the technical requirements for the cooling water of the induction coil of the medium frequency induction furnace?
Industrial pressure water is usually used for cooling. The cooling water pressure should be maintained at 0.15-0.20MPa, the water temperature should be maintained at an inlet
temperature of 20-35℃, and the outlet temperature should be lower than 55℃. If the cooling water temperature is too low, condensation will occur, and if the water temperature exceeds 55℃, the cooling capacity will be lost. In order to save water, a circulating cooling system can be used.